• defined lamp warm start within 1.5 s
• constant light output independent of fluctuations in mains voltage
• average life = 50,000 h (at ta max. and a failure rate of ≤ 0.2 % per 1,000 h)
• AC voltage range 198-264 V
• DC voltage range 176-280 V (for ignition input voltage ≥ 198 V DC)
• power factor ≥ 0.97
• overvoltage protection 320 V AC, 1 h
• overvoltage indication starting at input voltage ≥ 306 V AC
• undervoltage protection (shut down) < 150 V AC / 176 V DC
• operating frequency ≥ 40 kHz
• suitable for automatic and manual wiring with insulation displacement connector (IDC)
• wide operating temperature range (see table)
• suitable for use in emergency lighting installations in accordance with EN 50172
• safe switch off of defective lamps
• automatic re-start after lamp change
• for luminaires with or and in acc. with EN 60598, VDE 0710 and VDE 0711
• suitable for luminaires with safety class 1 and safety class 2
• ingress protection IP 20
• thermal protection according to EN 61347-2-3 C5e ( at 2x58 W